Advertisement

4.6 Application Selection

4.6

Application Selection

Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application
Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values
appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
Note:
1. Application Presets can only be selected if all drive parameters are at their original default settings.
2. Entering a value to A1-03 to enable an Application Preset will fix that value to the parameter. The value cannot be changed without first
setting A1-03 to 2220 or 3330 to initialize the drive.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter
A1-03 may automatically change the I/O terminal function from the default setting. Failure to comply may result in death or serious injury.
No.
A1-03
Initialize Parameters
A1-06
Application Presets (monitor only)
u

A1-03 = 8008: Pump

Parameter
A1-06
b1-01
b1-02
b1-03
b1-04
C1-01
C1-02
d1-01
E2-01
L2-01
L5-01
L5-04
o1-06
o1-07
o1-08
u

A1-03 = 8009: Pump w/ PI

Parameter
A1-06
b1-02
126
Parameter Name
Table 4.7 Pump Application Parameters
Name
Application Preset Selection (monitor only)
Frequency Reference Selection
Run Command Selection
Stopping Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Frequency Reference 1
Motor Rated Current
Momentary Power Loss Operation Selection
Number of Auto Restart Attempts
Fault Reset Interval Time
User Monitor Selection Mode
Second Line Monitor Selection
Third Line Monitor Selection
Table 4.8 Pump w/ PI Application Parameters
Name
Application Preset Selection (monitor only)
Run Command Selection
Settings
0: No initialization (default)
1110: User Initialize (parameter values
must be stored using parameter o2-03)
2220: 2-Wire Initialize
3330: 3-Wire Initialize
5550: Terminal/Control Initialize
8008: Pump
8009: Pump w/ PI
8010: Fan
8011: Fan w/ PI
0: Disabled
8: Pump
9: Pump w/ PI
10: Fan
11: Fan w/ PI
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
0
0
Page
126
147
148
149
151
177
177
182
195
240
254
255
268
268
268
Page