3.9 Control Circuit Wiring
Type
No.
Multi-function pulse train input
RP
(Frequency reference)
+V
Power supply for analog inputs
+24 Vdc transducer power supply for customer
24 V
use
Multi-function analog input 1
Analog Inputs /
A1
(Frequency reference bias)
Pulse Train
Input
Multi-function analog input 2
A2
(Frequency reference bias)
Multi-function analog input 3
A3
(Frequency reference bias)
AC
Frequency reference common
E (G) Ground for shielded lines and option cards
n
Output Terminals
Table 3.8
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.
Type
No.
MA
N.O.
Fault Relay
MB
N.C. output
Output
MC
Fault output common
MD
N.O.
ME
N.C. Output
MF
Common (Speed agree)
Multi-Function
Digital Output
M1
Multi-function digital output (During run)
<1>
M2
M3
Multi-function digital output (Zero speed)
M4
FM
Analog monitor output 1 (Output frequency)
Monitor
AM
Analog monitor output 2 (Output current)
Output
AC
Monitor common
<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching
life is estimated at 200,000 times (assumes 1 A, resistive load).
Connect a suppression diode as shown in
is greater than the circuit voltage.
A – External power, 48 V max.
B – Suppression diode
96
Terminal Name (Function)
Table 3.8 Control Circuit Output Terminals
Terminal Name (Function)
Figure 3.30
A
Figure 3.30 Connecting a Suppression Diode
Function (Signal Level) Default Setting
• Input frequency range: 0 to 32 kHz
• Signal Duty Cycle: 30 to 70%
• High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
• Input impedance: 3 kΩ
10.5 Vdc (max allowable current 20 mA)
150 mA maximum capacity
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-01.
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-09.
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-05.
0 V
Function (Signal Level) Default Setting
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
-10 to +10 Vdc, or 0 to +10 Vdc
0 V
when driving a reactive load such as a relay coil. Ensure the diode rating
B
C
D
C – Coil
D – 50 mA or less