YASKAWA P1000 Technical Manual page 149

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

• 2-Wire sequence 2:
Two inputs (Start/Stop-FWD/REV).
page
212.
• 3-Wire sequence:
Setting A1-03 to 3330 initializes the drive and presets terminals S1, S2, and S5 to Start, Stop, and FWD/REV.
Setting 0: 3-Wire Sequence on page
Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the Run command via serial communications by connecting the RS-485/RS-422 serial
communication cable to control terminals R+, R-, S+, and S- on the removable terminal block.
Configuration on page 506
Setting 3: Option Card
This setting requires entering the Run command via the communication option board by plugging a communication option
board into the CN5-A port on the control PCB. Refer to the option board manual for instructions on integrating the drive into
the communication system.
Note:
If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operation error will be displayed on the digital operator and
the drive will not run.
n
b1-03: Stopping Method Selection
Selects how the drive stops the motor when the Run command is removed or when a Stop command is entered.
No.
b1-03
Setting 0: Ramp to Stop
When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the
active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed Control,
or Short Circuit Braking.
Refer to b2-01: DC Injection Braking Start Frequency on page 153
Setting 1: Coast to Stop
When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to
stop. The stopping time is determined by the inertia and the friction in the driven system.
Note:
After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do
not enter Run command until it has come to a complete stop. Use DC Injection at Start
Start on page
153) or Speed Search
Setting 2: DC Injection Braking to Stop
When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time
(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC Injection Braking is set in
parameter b2-02 into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly
faster compared to Coast to Stop.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Refer to Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2 on
206.
for instructions.
Parameter Name
Stopping Method Selection
Run
command
ON
Output
frequency
Motor speed
Figure 5.3 Coast to Stop
(Refer to b3: Speed Search on page
Refer to MEMOBUS/Modbus
Setting Range
0 to 3
for details.
OFF
Drive output is shut off
(Refer to b2-03: DC Injection Braking Time at
153) to restart the motor before it has completely stopped.
5.2 b: Application
Refer to
Default
0
5
149