L6: Torque Detection - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

n
L5-02: Auto Restart Fault Output Operation Selection
Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.
No.
L5-02
Setting 0: No Fault Output
Run command
Fault condition
Fault display
Fault digital output
Output Frequency
(U1-02)
Setting 1: Fault Output Is Set
n
L5-04: Fault Reset Interval Time
Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.
No.
L5-04
n
L5-05: Fault Reset Operation Selection
No.
L5-05
Setting 0: Count Successful Restarts
The drive will continuously attempt to restart. If it restarts successfully, the restart counter is increased. This operation is
repeated each time a fault occurs until the counter reaches the value set to L5-01.
Setting 1: Count Restart Attempts
The drive will attempt to restart using the time interval set to parameter L5-04. A record is kept of the number of attempts to
restart to the drive, regardless of whether those attempts were successful. When the number of attempted restarts exceeds the
value set to L5-01, the drive stops attempting to restart.
u

L6: Torque Detection

The drive provides two independent torque detection functions that trigger an alarm or fault signal when the load is too heavy
(oL), or suddenly drops (UL). These functions are set up using the L6-oo parameters. Program the digital outputs as shown
below to indicate the underload or overload condition to an external device:
Note:
When overtorque occurs in the application, the drive may stop due to overcurrent (oC) or overload (oL1). To prevent the drive from stopping,
use torque detection to indicate an overload situation to the controller before oC or oL1 occur. Use undertorque detection to discover
application problems like a torn belt, a pump shutting off, or other similar trouble.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Name
Auto Restart Fault Output Operation Selection
Auto-Restart - Cancel Early
Fault output disabled (L5-02 = 0)
Figure 5.81 Auto Restart Cancel Early
Name
Fault Reset Interval Time
Name
Fault Reset Operation Selection
5.8 L: Protection Functions
Setting Range
0, 1
L5-04
Setting Range
0.5 to 600.0 s
Setting Range
0, 1
Default
0
Default
10.0 s
Default
0
5
255

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents