YASKAWA P1000 Technical Manual page 212

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

5.7 H: Terminal Functions
Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence
Configures the drive for a 2-Wire sequence.
When an input terminal set to 40 closes, the drive operates in the forward direction. When an input set for 41 closes, the drive
operates in reverse. Closing both inputs simultaneously will result in an external fault.
Note:
1. This function cannot be used simultaneously with settings 42 and 43.
2. The same functions are assigned to terminals S1 and S2 when the drive is initialized for 2-Wire sequence.
Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2
Sets the drive for 2-Wire sequence 2.
When an input terminal programmed for 42 closes, the drive will operate in the selected direction. The drive will stop when
the input opens.
The input programmed for 43 selects the direction. If the input is open, forward direction is selected. If the input is closed,
reverse direction is selected.
Note:
This function cannot be used simultaneously with settings 40 and 41.
Setting 47: Node Setup
If the SI-S3 option card is connected, closing this terminal sets a node address for operation on a CANopen network.
Setting 51: Sequence Timer Disable
Drive ignores sequence timers and runs normally (based on b1-02/b1-16 source).
Setting 52: Sequence Timer Cancel
The sequence timers are canceled.
Setting 60: DC Injection Braking Command
DC Injection Braking is activated when a DC Injection Braking command is input while the drive is stopped. DC Injection
Braking is released when a Run command or a Jog command is input.
Braking on page 152
for details on setting up the DC Injection Braking function.
The diagram below illustrates DC Injection Braking:
Setting 61, 62: External Speed Search Command 1, 2
These input functions enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start).
Activation on page 156
for details on how to use the input signals.
Speed Search.
Note:
Simultaneously assigning Speed Search 1 and Speed Search 2 to the input terminals will trigger an oPE03 error.
212
Forward Run
Reverse Run
Figure 5.43 Example Wiring Diagram for 2-Wire Sequence
OFF
DC Injection braking
command
OFF
FWD Run command
DC Injection
braking
Output frequency
Figure 5.44 DC Injection Braking Input Timing Diagram
Drive
S1
S2
Standard Digital
SN
Input Common
Refer to b2: DC Injection Braking and Short Circuit
ON
ON
DC Injection
braking
DC Injection Braking
Start Frequency
(b2-01)
Refer to b3: Speed Search on page 153
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
OFF
OFF
Refer to Speed Search
for more about

Hide quick links:

Advertisement

Table of Contents
loading