YASKAWA P1000 Technical Manual page 268

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

5.10 o: Operator Related Settings
n
o1-05: LCD Contrast Control
Sets the brightness of the digital operator. The lower the setting, the brighter the LCD contrast. The higher the setting, the
darker the LCD contrast.
Note:
Available in drive software versions PRG: 8503 and later.
No.
o1-05
n
o1-06: User Monitor Selection Mode
Select between standard sequential monitors or selectable monitors to be displayed on the 2nd and 3rd lines of the digital
operator display.
Use parameters o1-07 and o1-08 to select and fix the second and third monitors shown in the Home (Frequency Reference)
and Monitor screen to ensure that those monitors are always visible when scrolling through the monitor list.
No.
o1-06
Setting 0: 3 Mon Sequential (displays the next 2 sequential monitors)
Setting 1: 3 Mon Selectable (set by o1-07 and o1-08)
n
o1-07: Second Line User Monitor Selection
Selects the monitor that is shown in the second line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set "403" to display
monitor parameter U4-03.
No.
o1-07
n
o1-08: Third Line User Monitor Selection
Selects the monitor that is shown in the third line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set "403" to display
monitor parameter U4-03.
No.
o1-08
n
o1-09: Frequency Reference Display Units
Selects the monitor that is shown in the third line. Enter the last three digits of the monitor parameter number to be displayed:
Uo-oo. For example, set "403" to display monitor parameter U4-03.
Note:
Parameter is effective only when o1-06 is set to 1.
No.
o1-09
268
Name
LCD Contrast Control
Name
User Monitor Selection Mode
Name
Second Line User Monitor Selection
Name
Second Line User Monitor Selection
Name
Frequency Reference Display Units
Setting Range
0 to 5
Setting Range
0, 1
Setting Range
101 to 799
Setting Range
101 to 799
Setting Range
0 to 15; 24, 25
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
3
Default
0
Default
102
Default
103
Default
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents