In
Figure 5.91
S2-04 = 1, S2-05 = 0, S2-09 = 2, S2-10 = 1. It shows the effect of sequence timer disable input.
Run
command
Seq Timer
Cancel input
d1-01
Output
frequency
Sequence Timer 1
multi-function output
Sequence Timer 2
multi-function output
In
Figure 5.92
S2-04 = 1, S2-05 = 0, S2-09 = 2, S2-10 = 1. It shows the effect of sequence timer cancel input with run re-
cycle.
Run
command
Seq Timer
Cancel input
d1-01
Output
frequency
Sequence Timer 1
multi - function output
Sequence Timer 2
multi - function output
In
Figure 5.93
S2-04 = 1, S2-05 = 0, S2-09 = 2, S2-10 = 1. It shows the effect of HAND mode.
Run
command
HAND mode
d1-01
Output
frequency
Sequence Timer 1
multi-function output
Sequence Timer 2
multi-function output
n
S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time
Sets the start times for timers 1 to 4.
If the Stop Time is set to a higher value than the Start Time, the Sequence Timers will be active starting from the set Start
Time, run through midnight, and stop the following day at the set Stop Time.
Note:
Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer in drive software
versions PRG: 8551 and earlier.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Figure 5.91 Timing Chart 2
Figure 5.92 Timing Chart 3
HAND mode
freq ref
Figure 5.93 Timing Chart 4