E: Motor Parameters; E1: V/F Pattern - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.6 E: Motor Parameters
B.6 E: Motor Parameters
u

E1: V/f Pattern

No.
(Addr.
Name
Hex)
E1-01
Input Voltage Setting
(300)
E1-03
V/f Pattern Selection
(302)
E1-04
Maximum Output
(303)
Frequency
E1-05
Maximum Voltage
(304)
E1-06
Base Frequency
(305)
E1-07
Middle Output Frequency
(306)
E1-08
Middle Output Frequency
(307)
Voltage
E1-09
Minimum Output Frequency
(308)
E1-10
Minimum Output Frequency
(309)
Voltage
E1-11
(30A)
Middle Output Frequency 2
<4>
E1-12
Middle Output Frequency
(30B)
Voltage 2
<4>
E1-13
Base Voltage
(30C)
<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<4> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
446
This parameter must be set to the power supply voltage.
WARNING! Electrical Shock Hazard. Drive input voltage (not motor
voltage) must be set in E1-01 for the protective features of the drive to
function properly. Failure to do so may result in equipment damage
and/or death or personal injury.
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 1
7: 60 Hz, Variable torque 2
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f, E1-04 through E1-13 settings define the V/f pattern
These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E1-07 and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
Description
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Values
Page
<1>
Default: 230 V
Min.: 155
191
<1>
Max.: 255
<2>
Default: F
191
Range: 0 to 9;
A to FF
Default: 60.0 Hz
Min.: 40.0
194
Max.: 400.0
<1>
Default: 575 V
194
Min.: 0.0
Max.: 255.0
Default: 60.0 Hz
Min.: 0.0
194
Max.: E1-04
Default: 3.0 Hz
Min.: 0.0
194
Max.: E1-04
<1>
Default: 15.0 V
194
Min.: 0.0 V
Max.: 255.0 V
Default: 1.5 Hz
Min.: 0.0
194
Max.: E1-04
<1>
Default: 9.0 V
194
Min.: 0.0 V
Max.: 255.0 V
Default: 0.0 Hz
Min.: 0.0
194
Max.: E1-04
Default: 0.0 V
Min.: 0.0
194
<1>
Max.: 255.0 V
<3>
Default: 0.0 V
Min.: 0.0
194
<1>
Max.: 255.0 V