YASKAWA P1000 Technical Manual page 317

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

Digital Operator Display
rUn
Cause
A motor switch command was entered
during run.
Digital Operator Display
Cause
A digital input set to 67H (MEMOBUS/
Modbus test) was closed while the drive
was running.
Digital Operator Display
TrPC
Cause
IGBTs have reached 90% of their expected
performance life.
Digital Operator Display
Cause
Phase loss in the drive input power.
Loose wiring in the drive input power
terminals.
There is a problem with the drive input
power voltage.
Drive internal circuitry is worn.
The drive input power transformer is too
small and voltage drops when the power is
switched on.
Air inside the drive is too hot.
The CHARGE light is broken or
disconnected.
Digital Operator Display
WrUn
Cause
The Run command has been applied and
the b1-11 timer is active.
Digital Operator Display
1PH
1-Phase Foldback
<0x5A>
Cause
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Motor Switch during Run
A command to switch motors was entered during run.
Change the operation pattern so that the motor switch command is entered while the drive is stopped.
MEMOBUS/Modbus Communication Test Mode Error
SE
Note:
This alarm will not trigger a multi-function output terminal that is set for alarm output
(H2-oo = 10).
Stop the drive and run the test again.
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Replace the drive.
Undervoltage
One of the following conditions was true when the drive was stopped and a Run command was entered:
• DC bus voltage dropped below the level specified in L2-05.
Uv
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage
is under L2-05.
Check for wiring errors in the main circuit drive input power. Correct the wiring.
• Ensure the terminals have been properly tightened.
• Apply the tightening torque to the terminals as specified.
Tightening Torques on page
• Check the voltage.
• Lower the voltage of the drive input power so that it is within the limits listed in the specifications.
• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or your nearest sales representative.
• Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed.
• Check the capacity of the drive input power transformer.
Check the temperature inside the drive.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
Waiting for Run
Adjust b1-11 to the desired delay time. The drive sill start normally after the b1-11 timer expires.
Output speed is being limited because of excessive DC bus voltage ripple.
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
Refer to Main Circuit Wire Gauges and
85.
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
6.5 Alarm Detection
317