Peripheral Installation
Door Lock Control with DDCB and HDCB
In addition to the option interface PCB (PIOU, PIOUS, PEPU), each DDCB can provide one
door lock control.
N
DDCB and HDCB/DRLK Assignments Guide
Table 6-1
PDKU
Door Lock 1
Door Lock 2
Door Lock 3
Door Lock 4
Important!
H
Configure Each DDCB for the Door Lock Control Function
1.
2.
3.
4.
C
Note
5.
6.
7.
8.
6-14
Strata CT DDCBs connect only to digital circuits (always circuit 5 on a PDKU)
associated with ports 004, 012, 020, and 028.
DDCB/HDCB
Number
1
2
3
4
Each DDCB door lock control reduces the maximum door phone capacity by
one.
Connect the door lock wire pair to the DDCB modular B-jack (pins 3 and 4).
Set SW1 to the DOOR position.
Set SW2 to the LOCK position.
SW3 inside the DDCB can be set to open or close the door lock relay whenever a door
lock button is pressed: if SW3 is in the "1-2" position, the relay closes when the button
is pressed; if in the "2-3" position, the door lock relay opens when the button is pressed.
SW3 comes from the factory in the "1-2" position.
In Program 77-1, set the door lock activation for three or six seconds and enable the
PDKU ports for DDCB connection.
In Program 77-2, enable the DDCB B-jack for door lock operation.
In Program 39, assign door lock buttons to stations per the customer's record sheet.
Check each telephone door lock button from each station: the DDCB modular B-jack
(pins 3 and 4) will momentarily open or close (three or six seconds) when the button is
pressed.
Port
Program 39 Button Assignments
Number
004
Unlock Door 1 (DRLK 1), Code 72
012
Unlock Door 2 (DRLK 2), Code 73
020
Unlock Door 3 (DRLK 3), Code 74
028
Unlock Door 4 (DRLK 4), Code 75
Strata CT I&M Manual October 2000