Programming
6 Programming
6.1 How to Programme the Frequency
Converter
6.1.1 Quick Setup Parameters
0-01 Language
Option:
Function:
Defines the language to be used in the
display. The frequency converter can be
delivered with 4 different language
packages. English and German are
included in all packages. English cannot be
erased or manipulated.
[0]
English
Part of Language packages 1 - 4
*
[1]
Deutsch
Part of Language packages 1 - 4
[2]
Francais
Part of Language package 1
[3]
Dansk
Part of Language package 1
[4]
Spanish
Part of Language package 1
[5]
Italiano
Part of Language package 1
[6]
Svenska
Part of Language package 1
[7]
Nederlands
Part of Language package 1
[10] Chinese
Part of Language package 2
[20] Suomi
Part of Language package 1
[22] English US
Part of Language package 4
[27] Greek
Part of Language package 4
[28] Bras.port
Part of Language package 4
[36] Slovenian
Part of Language package 3
[39] Korean
Part of Language package 2
[40] Japanese
Part of Language package 2
[41] Turkish
Part of Language package 4
[42] Trad.Chinese
Part of Language package 2
[43] Bulgarian
Part of Language package 3
[44] Srpski
Part of Language package 3
[45] Romanian
Part of Language package 3
[46] Magyar
Part of Language package 3
[47] Czech
Part of Language package 3
[48] Polski
Part of Language package 4
[49] Russian
Part of Language package 3
MG37A202
Operating Instructions
0-01 Language
Option:
[50] Thai
[51] Bahasa
Indonesia
1-20 Motor Power [kW]
Range:
4.00
kW
*
1-22 Motor Voltage
Range:
Size
related
*
1-23 Motor Frequency
Range:
50.
Hz
1000
*
Hz]
1-24 Motor Current
Range:
Size
related
*
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
Function:
Part of Language package 2
Part of Language package 2
Function:
[0.09 -
Enter the nominal motor power in kW
3000.00
according to the motor nameplate data.
kW]
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running. This parameter is
visible in LCP if 0-03 Regional Settings is [0]
International .
NOTICE
Four sizes down, one size up from
nominal unit rating.
Function:
[ 10 -
Enter the nominal motor voltage
1000 V]
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running.
Function:
[20 -
Min - Max motor frequency: 20 - 1000Hz.
Select the motor frequency value from the
motor nameplate data. If a value different from
50 Hz or 60 Hz is selected, it is necessary to
adapt the load independent settings in
1-50 Motor Magnetisation at Zero Speed to
1-53 Model Shift Frequency. For 87 Hz operation
with 230/400 V motors, set the nameplate data
for 230V/50 Hz. Adapt 4-13 Motor Speed High
Limit [RPM] and parameter 3-03 Maximum
Reference to the 87 Hz application.
Function:
[ 0.10 -
Enter the nominal motor current
10000.00 A]
value from the motor nameplate
data. This data is used for
calculating motor torque, motor
thermal protection etc.
6
6
49
Need help?
Do you have a question about the VLT FC 302 and is the answer not in the manual?