Danfoss VLT FC 302 Operating Instructions Manual page 134

Low harmonic drive 132-630 kw
Hide thumbs Also See for VLT FC 302:
Table of Contents

Advertisement

Warnings and Alarms
No.
Description
79
Illegal PS config
80
Unit initialised to default value
250
New spare part
251
New type code
300
Mains cont. fault
301
SC cont. fault
302
Cap. over current
303
Cap. earth fault
304
DC over current
305
Mains freq. limit
306
Compensation Limit
308
Resistor temp
309
Mains earth fault
311
Switch. freq. limit
312
CT range
314
Auto CT interrupt
315
Auto CT error
316
CT location error
317
CT polarity error
318
CT ratio error
Table 9.3 Alarm/Warning Code List
9
9
A trip is the action when an alarm has appeared. The trip disables the active filter and can be reset by pressing [Reset] or
make a reset by a digital input (parameter group 5-1* Digital Inputs [1] Reset). The origin event that caused an alarm cannot
damage the active filteror cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause
damage to active filter or connected parts. A Trip Lock situation can only be reset by a power cycling.
Warning
Alarm
Trip locked
Table 9.4 LED Indicator Lights
132
Operating Instructions
Warning
X
X
X
X
X
X
X
X
X
X
yellow
flashing red
yellow and red
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
Alarm/Trip
Alarm/Trip Lock
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Parameter Reference