System Start Up - Danfoss VLT FC 302 Operating Instructions Manual

Low harmonic drive 132-630 kw
Hide thumbs Also See for VLT FC 302:
Table of Contents

Advertisement

Start Up and Functional Tes...
NOTICE
Chapter 4.1 Pre-start and chapter 4.3 Basic Operational
Programming conclude the procedures for applying
power to the frequency converter, basic programming,
set-up, and functional testing.

4.5 System Start Up

Complete user wiring and application programming before
performing the procedure in this section. See
chapter 7 Application Examples for application set-up
information. The following procedure is recommended
after application set-up by the user is completed.
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment are ready for start. It is the responsibility of
the user to ensure safe operation under any condition.
Failure to ensure that the motor, system, and any
attached equipment are ready for start could result in
personal injury or equipment damage.
1.
Press [Auto On].
2.
Ensure that external control functions are
properly wired to the frequency converter and all
programming is completed.
3.
Apply an external run command.
4.
Adjust the speed reference throughout the speed
range.
5.
Remove the external run command.
6.
Note any problem.
If warnings or alarms occur, see chapter 9 Warnings and
Alarms.
MG37A202
Operating Instructions
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
4
4