Danfoss VLT FC 302 Operating Instructions Manual page 118

Low harmonic drive 132-630 kw
Hide thumbs Also See for VLT FC 302:
Table of Contents

Advertisement

Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
7
7
39
01
02
03
04
05
06
Table 7.13 Using SLC to Set a Relay
116
Operating Instructions
Parameters
Function
Setting
4-30 Motor
[1] Warning
Feedback Loss
Function
4-31 Motor
100 RPM
Feedback Speed
Error
4-32 Motor
5 s
Feedback Loss
Timeout
7-00 Speed PID
[2] MCB 102
Feedback Source
17-11 Resolution
1024*
(PPR)
13-00 SL
[1] On
Controller Mode
13-01 Start Event [19] Warning
13-02 Stop Event [44] Reset
key
13-10 Comparato
[21] Warning
r Operand
no.
13-11 Comparato
[1] ≈*
r Operator
13-12 Comparato
90
r Value
13-51 SL
[22]
Controller Event
Comparator 0
13-52 SL
[32] Set
Controller Action
digital out A
low
Parameter 5-40 F
[80] SL digital
unction Relay
output A
*=Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 is issued. The SLC monitors
Warning 90 and in the case
that Warning 90 becomes TRUE
then relay 1 is triggered.
External equipment may
indicate that service is required.
If the feedback error goes
below the limit again within 5
s, the frequency converter
continues and the warning
disappears. But relay 1 is still
triggered until [Reset] on the
LCP.
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 7.14 Mechanical Brake Control (Open Loop)
1-76
Current
Speed
1-71
Start (18)
Start
reversing (19)
Relay output
Open
Closed
Illustration 7.4 Mechanical Brake Control (Open Loop)
Parameters
Function
Setting
1-00 Configu-
[0] Speed
ration Mode
open loop
1-01 Motor
+
[1] VVC
Control Principle
Parameter 5-40 F
[32] Mech.
unction Relay
brake ctrl.
5-10 Terminal 18
[8] Start*
Digital Input
5-11 Terminal 19
[11] Start
Digital Input
reversing
1-71 Start Delay
0.2
1-72 Start
+
[5] VVC
/
Function
FLUX
Clockwise
1-76 Start
I
m,n
Current
Parameter 2-20 R
App.
elease Brake
dependent
Current
Parameter 2-21 A
Half of
ctivate Brake
nominal slip
Speed [RPM]
of the motor
*=Default Value
Notes/comments:
Time
2-21
1-71
2-21
MG37A202

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 302 and is the answer not in the manual?