Commissioning

6.4 Programming the Drive

For detailed information on the key functions on the local
control panel (LCP), see chapter 3.6 Local Control Panel
(LCP). For information on parameter settings, see the
programming guide.
Parameter overview
Parameter settings control the operation of the drive, and
are accessed via the LCP. These settings are assigned a
default value at the factory, but can be configured for their
unique application. Each parameter has a name and
number that remain the same regardless of the
programming mode.
6
6
In the Main Menu mode, the parameters are divided into
groups. The first digit of the parameter number (from the
left) indicates the parameter group number. The parameter
group is then broken down into subgroups, if necessary.
For example:
0-** Operation/Display
0-0* Basic Settings
Parameter 0-01 Language
Parameter 0-02 Motor Speed Unit
Parameter 0-03 Regional Settings
Table 6.2 Example of Parameter Group Hierarchy
Moving around parameters
Navigate through the parameters using the following LCP
keys:
Press [
Press [◄] [►] to shift a space to the left or right of
a decimal point while editing a decimal
parameter value.
Press [OK] to accept the change.
Press [Cancel] to disregard the change and exit
edit mode.
Press [Back] twice to show the status view.
Press [Main Menu] once to go back to the main
menu.
6.4.1 Entering System Information
NOTICE
SOFTWARE DOWNLOAD
For commissioning via PC, install MCT 10 Set-up
Software. The software is available for download (basic
version) or for ordering (advanced version, code number
130B1000). For more information and downloads, see
www.danfoss.com/en/service-and-support/downloads/dds/
vlt-motion-control-tool-mct-10/.
48
VLT® AutomationDrive FC 302
Parameter group
Parameter subgroup
Parameter
Parameter
Parameter
] [
] to scroll up or down.
Danfoss A/S © 04/2018 All rights reserved.
The following steps are used to enter basic system
information into the drive. Recommended parameter
settings are intended for start-up and checkout purposes.
Application settings vary.
NOTICE
Although these steps assume that an asynchronous
motor is used, a permanent magnet motor can be used.
For more information on specific motor types, see the
product-specific programming guide.
1.
Press [Main Menu] on the LCP.
2.
Select 0-** Operation/Display and press [OK].
3.
Select 0-0* Basic Settings and press [OK].
4.
Select parameter 0-03 Regional Settings and
press [OK].
5.
Select [0] International or [1] North America as
appropriate and press [OK]. (This action changes
the default settings for some basic parameters).
6.
Press [Quick Menus] on the LCP and then select
02 Quick Setup.
7.
Change the following parameters settings listed
in Table 6.3 if necessary. The motor data is found
on the motor nameplate.
Parameter
Parameter 0-01 Language
Parameter 1-20 Motor Power [kW]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 5-12 Terminal 27 Digital Input
Parameter 3-02 Minimum Reference
Parameter 3-03 Maximum Reference
Parameter 3-41 Ramp 1 Ramp up Time
Parameter 3-42 Ramp 1 Ramp Down Time
Parameter 3-13 Reference Site
Parameter 1-29 Automatic Motor Adaptation
(AMA)
Table 6.3 Quick Setup Settings
NOTICE
MISSING INPUT SIGNAL
When the LCP shows AUTO REMOTE COASTING or alarm
60, External Interlock, the unit is ready to operate but is
missing an input signal. See chapter 5.8.5 Enabling Motor
Operation (Terminal 27) for details.
Default setting
English
4.00 kW
400 V
50 Hz
9.00 A
1420 RPM
Coast inverse
0.000 RPM
1500.000 RPM
3.00 s
3.00 s
Linked to Hand/
Auto
Off
MG38A202