Remote Reset - Mitsubishi Electric MELSEC iQ-R Series User Manual

Cc-link ie field network remote head module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Remote RESET

This function remotely resets the remote head module without switch operation when the remote head module is in STOP
state (including when either a moderate or major error occurs in the remote head module).
Even when the switch of the remote head module is at the RUN position, this function can reset the module if
it is in the STOP state.
Remote RESET setting
Remote reset can be disabled.
[Navigation window]  [Parameter]  [RJ72GF15-T2]  [CPU Parameter]  [Operation Related Setting]  [Remote
Reset Setting]
Window
Displayed items
Item
Remote Reset
*1 The default differs from that of the CPU module. Care should be taken when performing remote set through all stations specification.
Executing method
The following methods are available.
■Using an engineering tool
• From the menu, open the "Remote Operation" window to execute the function. ( GX Works3 Operating Manual)
[Online]  [Remote Operation]
• Execute the function using the CC-Link IE Field Network diagnostics. ( Page 96 Remote operation)
■By an external device using SLMP
Execute the function with the SLMP command. ( SLMP Reference Manual)
1 FUNCTIONS
28
1.3 Remote Operation
Description
Set when externally resetting the remote head module.
Setting range
• Disable
• Enable
*1
(Default: Enable
)

Advertisement

Table of Contents
loading

Table of Contents