Functionality; Function Block; Signals; Settings - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 14
Station communication
14.8.2
14.8.3
14.8.4
14.8.5
Table 367:
GOOSESPRCV Non group settings (basic)
Name
Operation
14.8.6
448

Functionality

GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.

Function block

GOOSESPRCV
BLOCK
DATAVALID
COMMVALID
IEC10000248-1-en.vsd
IEC10000248 V1 EN
Figure 199:
GOOSESPRCV function block

Signals

Table 365:
GOOSESPRCV Input signals
Name
BLOCK
Table 366:
GOOSESPRCV Output signals
Name
SPOUT
DATAVALID
COMMVALID
TEST

Settings

Values (Range)
Unit
Off
-
On

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
^SPOUT
TEST
Type
Default
Description
BOOLEAN
0
Type
Description
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Step
Default
-
Off
1MRK 505 288-UEN A
Block of function
Single point output
Data valid for single point output
Communication valid for single point output
Test output
Description
Operation Off/On
Technical manual