Technical Data; Indications; Functionality - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
12.4.7
12.5
12.5.1
Technical manual

Technical data

Table 285:
DRPRDRE technical data
Function
Current recording
Voltage recording
Pre-fault time
Post-fault time
Limit time
Maximum number of recordings
Time tagging resolution
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of phasors in the
Trip Value recorder per recording
Maximum number of indications in a
disturbance report
Maximum number of events in the
Event recording per recording
Maximum number of events in the
Event list
Maximum total recording time (3.4 s
recording time and maximum number
of channels, typical value)
Sampling rate
Recording bandwidth

Indications

Functionality

To get fast, condensed and reliable information about disturbances in the primary and/
or in the secondary system it is important to know, for example binary signals that
have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance recorder function (triggered).
The Indication list function shows all selected binary input signals connected to the
Disturbance recorder function that have changed status during a disturbance.
Range or value
-
-
(0.05–3.00) s
(0.1–10.0) s
(0.5–8.0) s
100, first in - first out
1 ms
30 + 10 (external + internally
derived)
96
30
96
150
1000, first in - first out
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
1 kHz at 50 Hz
1.2 kHz at 60 Hz
(5-300) Hz
Section 12
Monitoring
Accuracy
± 1,0% of I
at I ≤ I
r
r
± 1,0% of I at I > Ir
± 1,0% of U
at U ≤ U
r
r
± 1,0% of U at U > U
r
-
-
-
-
See time synchronization
technical data
-
-
-
-
-
-
-
-
-
375