Table 319:
SSCBR Technical data
Function
Alarm levels for open and close
travel time
Alarm levels for number of
operations
Setting of alarm for spring
charging time
Time delay for gas pressure
alarm
Time delay for gas pressure
lockout

Measurands for IEC 60870-5-103 I103MEAS

Functionality

103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The measurand reporting interval set for MMXU function blocks, using the
xDbRepInt and xAngDbRepInt settings, must be coordinated with the event reporting
interval set for the IEC 60870-5-103 communication using setting CycMeasRepTime.
Range or value
(0-200) ms
(0 - 9999)
(0.00-60.00) s
(0.00-60.00) s
(0.00-60.00) s
Section 12
Monitoring
Accuracy
± 0.5% ± 25 ms
-
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms