Signals; Settings; Operation Principle - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
11.7.4
11.7.5
11.7.6
Technical manual

Signals

Table 223:
IB16A Input signals
Name
Type
BLOCK
BOOLEAN
INP
INTEGER
Table 224:
IB16A Output signals
Name
Type
OUT1
BOOLEAN
OUT2
BOOLEAN
OUT3
BOOLEAN
OUT4
BOOLEAN
OUT5
BOOLEAN
OUT6
BOOLEAN
OUT7
BOOLEAN
OUT8
BOOLEAN
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN

Settings

The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)

Operation principle

With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the
remaining OUTx = 0 for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in
accordance with the table IB16A_1. When not activated the OUTx has the value 0.
In the above example when integer 15 is on the input INP the OUT1 has a value =1,
OUT2 has a value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of
these OUTx is equal to 1 + 2 + 4 + 8 = 15.
Default
Description
0
Block of function
0
Integer Input
Description
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Section 11
Logic
301