ABB Relion 650 Series REB650 Technical Manual page 258

Busbar protection
Table of Contents

Advertisement

Section 10
Control
252
The interlocking module is connected to the surrounding functions within a bay as
shown in figure 108.
Interlocking
modules in
other bays
Interlocking
module
en04000526.vsd
IEC04000526 V1 EN
Figure 108:
Interlocking module on bay level
Bays communicate via the station bus and can convey information regarding the
following:
Unearthed busbars
Busbars connected together
Other bays connected to a busbar
Received data from other bays is valid
Figure
109
illustrates the data exchange principle.
Bay 1
Disc QB1 and QB2 closed
WA1 not earthed
WA2 not earthed
WA1 and WA2 interconn
WA1
WA2
QB1
QB2
QA1
QB9
IEC05000494 V1 EN
Figure 109:
Data exchange between interlocking modules
Apparatus control
modules
SCILO
SCSWI
SXSWI
Apparatus control
modules
SCILO
SCSWI
SXCBR
Apparatus control
modules
SCILO
SCSWI
SXSWI
Station bus
Bay n
Disc QB1 and QB2 closed
. . .
WA1 not earthed
WA2 not earthed
WA1 and WA2 interconn
. .
QB1
QB2
QA1
QB9
1MRK 505 288-UEN A
Bus coupler
WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
WA1 and WA2 interconn
in other bay
QB2
QB1
QC1
QA1
en05000494.vsd
Technical manual
QC2

Advertisement