Settings - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 10
Control
10.1.5
Table 97:
SESRSYN Group settings (basic)
Name
Operation
CBConfig
URatio
PhaseShift
OperationSynch
Table continues on next page
164
Name
B2SEL
LN1SEL
LN2SEL
SYNPROGR
SYNFAIL
FRDIFSYN
FRDERIVA
UOKSC
UDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN

Settings

Values (Range)
Unit
Off
-
On
No voltage sel.
-
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
0.500 - 2.000
-
-180 - 180
Deg
Off
-
On
Type
Description
BOOLEAN
Bus2 selected
BOOLEAN
Line1 selected
BOOLEAN
Line2 selected
BOOLEAN
Synchronizing in progress
BOOLEAN
Synchronizing failed
BOOLEAN
Frequency difference out of limit for synchronizing
BOOLEAN
Frequency derivative out of limit for synchronizing
BOOLEAN
Voltage amplitudes above set limits
BOOLEAN
Voltage difference out of limit
BOOLEAN
Frequency difference out of limit for Auto operation
BOOLEAN
Phase angle difference out of limit for Auto
operation
BOOLEAN
Frequency difference out of limit for Manual
operation
BOOLEAN
Phase angle difference out of limit for Manual
Operation
BOOLEAN
Inadvertent circuit breaker closing
REAL
Calculated difference of voltage in p.u of set
voltage base value
REAL
Calculated difference of frequency
REAL
Calculated difference of phase angle
REAL
Bus voltage
REAL
Line voltage
INTEGER
Selected mode for automatic energizing
INTEGER
Selected mode for manual energizing
Step
Default
-
Off
-
No voltage sel.
0.001
1.000
1
0
-
Off
1MRK 505 288-UEN A
Description
Operation Off / On
Select CB configuration
Multiplication factor for minor internal
adjustmernt of measured line voltage for
synchro functions
Additional phase angle for selected line
voltage
Operation for synchronizing function
Off/On
Technical manual