Settings; Function Status Fault Protection For Iec 60870-5-103; I103Fltprot; Functionality - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
12.21.4
Table 327:
I103EF Non group settings (basic)
Name
Values (Range)
FunctionType
12.22
12.22.1
Technical manual

Settings

Unit
1 - 255
-

Function status fault protection for IEC 60870-5-103

I103FLTPROT

Functionality

I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.
Step
Default
1
160
Section 12
Monitoring
Description
Function type (1-255)
419