Section 15
Basic IED functions
15.3.3
15.3.3.1
15.3.3.2
15.3.3.3
15.3.3.4
470
Parameter setting groups ACTVGRP
Identification
Function description
Parameter setting groups
Function block
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
SETCHGD
IEC09000064_en_1.vsd
IEC09000064 V1 EN
Figure 208:
ACTVGRP function block
Signals
Table 387:
ACTVGRP Input signals
Name
Type
ACTGRP1
BOOLEAN
ACTGRP2
BOOLEAN
ACTGRP3
BOOLEAN
ACTGRP4
BOOLEAN
Table 388:
ACTVGRP Output signals
Name
Type
GRP1
BOOLEAN
GRP2
BOOLEAN
GRP3
BOOLEAN
GRP4
BOOLEAN
SETCHGD
BOOLEAN
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
IEC 61850
IEC 60617
identification
identification
ACTVGRP
-
Default
Description
0
Selects setting group 1 as active
0
Selects setting group 2 as active
0
Selects setting group 3 as active
0
Selects setting group 4 as active
Description
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Pulse when setting changed
1MRK 505 288-UEN A
ANSI/IEEE C37.2
device number
-
Technical manual