Goose Function Block To Receive A Double Point Value Goosedprcv; Identification; Functionality; Function Block - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
14.5
14.5.1
14.5.2
14.5.3
14.5.4
Technical manual
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the binary values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the OUTxVAL
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then
the OUTxVAL output will be LOW.
GOOSE function block to receive a double point
value GOOSEDPRCV

Identification

Function description
GOOSE function block to receive a
double point value

Functionality

GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.

Function block

GOOSEDPRCV
BLOCK
^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249-1-en.vsd
IEC10000249 V1 EN
Figure 196:
GOOSEDPRCV function block

Signals

Table 356:
GOOSEDPRCV Input signals
Name
Type
BLOCK
BOOLEAN
Station communication
IEC 61850
IEC 60617
identification
identification
GOOSEDPRCV
-
Default
Description
0
Block of function
Section 14
ANSI/IEEE C37.2
device number
-
443