Settings; Circuit Switch Sxswi; Signals - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
10.2.3.2
Table 106:
SXCBR Non group settings (basic)
Name
Values (Range)
tStartMove
tIntermediate
AdaptivePulse
tOpenPulse
tClosePulse
SuppressMidPos
10.2.4
10.2.4.1
Technical manual
Table 105:
SXCBR Output signals
Name
XPOS
EXE_OP
EXE_CL
OP_BLKD
CL_BLKD
UPD_BLKD
POSITION
OPENPOS
CLOSEPOS
TR_POS
CNT_VAL
L_CAUSE

Settings

Unit
0.000 - 60.000
s
0.000 - 60.000
s
Not adaptive
-
Adaptive
0.000 - 60.000
s
0.000 - 60.000
s
Off
-
On

Circuit switch SXSWI

Signals

Table 107:
SXSWI Input signals
Name
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
Table continues on next page
Type
Description
GROUP SIGNAL
Group connection to CSWI
BOOLEAN
Executes the command for open direction
BOOLEAN
Executes the command for close direction
BOOLEAN
Indication that the function is blocked for open
commands
BOOLEAN
Indication that the function is blocked for close
commands
BOOLEAN
Update of position indication is blocked
INTEGER
Apparatus position indication
BOOLEAN
Apparatus open position
BOOLEAN
Apparatus closed position
INTEGER
Truck position indication
INTEGER
Operation counter value
INTEGER
Latest value of the error indication during command
Step
Default
0.001
0.100
0.001
0.150
-
Not adaptive
0.001
0.200
0.001
0.200
-
On
Type
Default
Description
BOOLEAN
0
Block of function
BOOLEAN
0
Local/Remote switch indication from switchyard
BOOLEAN
0
Pulsed signal used to immediately open the switch
BOOLEAN
0
Pulsed signal used to immediately close the switch
BOOLEAN
0
Signal to block the open command
Section 10
Description
Supervision time for the apparatus to
move after a command
Allowed time for intermediate position
Output resets when a new correct end
position is reached
Output pulse length for open command
Output pulse length for close command
Mid-position is suppressed during the
time tIntermediate
Control
181

Advertisement

Table of Contents
loading

Table of Contents