Functionality; Function Block; Signals; Settings - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
14.6.2
14.6.3
14.6.4
14.6.5
Table 361:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Operation
14.6.6
Technical manual

Functionality

GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.

Function block

GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
IEC10000250-1-en.vsd
IEC10000250 V1 EN
Figure 197:
GOOSEINTRCV function block

Signals

Table 359:
GOOSEINTRCV Input signals
Name
BLOCK
Table 360:
GOOSEINTRCV Output signals
Name
INTOUT
DATAVALID
COMMVALID
TEST

Settings

Unit
Off
-
On

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
TEST
Type
Default
Description
BOOLEAN
0
Block of function
Type
Description
INTEGER
Integer output
BOOLEAN
Data valid for integer output
BOOLEAN
Communication valid for integer output
BOOLEAN
Test output
Step
Default
-
Off
Section 14
Station communication
Description
Operation Off/On
445