Monitored Data - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 10
Control
Table 98:
SESRSYN Non group settings (basic)
Name
GblBaseSelBus
GblBaseSelLine
SelPhaseBus1
SelPhaseBus2
SelPhaseLine1
SelPhaseLine2
10.1.6
166
Values (Range)
Unit
1 - 6
-
1 - 6
-
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1
-
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence

Monitored data

Table 99:
SESRSYN Monitored data
Name
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
Step
Default
1
1
1
1
-
Phase L1
-
Phase L1
-
Phase L1
-
Phase L1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
1MRK 505 288-UEN A
Description
Selection of one of the Global Base Value
groups, Bus
Selection of one of the Global Base Value
groups, Line
Select phase for busbar1
Select phase for busbar2
Select phase for line1
Select phase for line2
Unit
Description
-
Calculated difference of
voltage in p.u of set
voltage base value
Hz
Calculated difference of
frequency
deg
Calculated difference of
phase angle
kV
Bus voltage
kV
Line voltage
Technical manual

Advertisement

Table of Contents
loading