Functionality; Function Block; Signals - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
12.15.2
12.15.3
12.15.4
Technical manual

Functionality

Insulation gas monitoring function SSIMG is used for monitoring the circuit breaker
condition. Binary information based on the gas pressure in the circuit breaker is used
as input signals to the function. In addition, the function generates alarms based on
received information.

Function block

SSIMG
BLOCK
PRESSURE
BLK_ALM
PRES_ALM
PRESSURE
PRES_LO
TEMP
TEMP
PRES_ALM
TEMP_ALM
PRES_LO
TEMP_LO
SET_P_LO
SET_T_LO
RESET_LO
IEC09000129-1-en.vsd
IEC09000129 V1 EN
Figure 168:
SSIMG function block

Signals

Inputs PRESSURE and TEMP together with settings PressAlmLimit,
PressLOLimit, TempAlarmLimit and TempLOLimit are not supported
in this release of 650 series.
Table 307:
SSIMG Input signals
Name
Type
BLOCK
BOOLEAN
BLK_ALM
BOOLEAN
PRESSURE
REAL
TEMP
REAL
PRES_ALM
BOOLEAN
PRES_LO
BOOLEAN
SET_P_LO
BOOLEAN
SET_T_LO
BOOLEAN
RESET_LO
BOOLEAN
Default
Description
0
Block of function
0
Block all the alarms
0.0
Pressure input from CB
0.0
Temperature of the insulation medium from CB
0
Pressure alarm signal
0
Pressure lockout signal
0
Set pressure lockout
0
Set temperature lockout
0
Reset pressure and temperature lockout
Section 12
Monitoring