Outputs; Outputs For Tripping, Controlling And Signalling - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 16
IED physical connections
16.3
16.3.1
504
Table 426:
Binary inputs X339, 3U full 19"
Terminal
Description
X339-1
- for input 1
X339-2
Binary input 1 +
X339-3
-
X339-4
Common - for inputs 2-3
X339-5
Binary input 2 +
X339-6
Binary input 3 +
X339-7
-
X339-8
Common - for inputs 4-5
X339-9
Binary input 4 +
X339-10
Binary input 5 +
X339-11
-
X339-12
Common - for inputs 6-7
X339-13
Binary input 6 +
X339-14
Binary input 7 +
X339-15
-
X339-16
Common - for inputs 8-9
X339-17
Binary input 8 +
X339-18
Binary input 9 +

Outputs

Outputs for tripping, controlling and signalling

Output contacts PO1, PO2 and PO3 are power output contacts used, for example, for
controlling circuit breakers.
Each signal connector terminal is connected with one 0.5...2.5 mm
2
0.5...1.0 mm
wires.
The connected DC voltage to outputs with trip circuit supervision
(TCS) must have correct polarity or the trip circuit supervision
TCSSCBR function will not operate properly.
1MRK 505 288-UEN A
PCM600 info
Hardware module
Hardware channel
instance
BIO_6
BI1
BIO_6
BI1
BIO_6
BI2
BIO_6
BI3
BIO_6
BI4
BIO_6
BI5
BIO_6
BI6
BIO_6
BI7
BIO_6
BI8
BIO_6
BI9
2
wire or with two
Technical manual