Logic
11.9.2
11.9.3
11.9.4
306

Functionality

Elapsed Time Integrator (TEIGGIO) function is a function that accumulates the
elapsed time when a given binary signal has been high.
The main features of TEIGGIO are
Applicable to long time integration (≤999 999.9 seconds).
Supervision of limit transgression conditions and overflow.
Possibility defining a warning or alarm with the resolution of 10 milliseconds.
Retain the integration value at a warning/alarm/overflow.
Possibilities for blocking and reset.
Report the integrated time

Function block

TEIGGIO
BLOCK
WARNING
IN
ALARM
RESET
OVERFLOW
ACCTIME
IEC13000005-1-en.vsd
IEC13000005 V1 EN
Figure 139:
TEIGGIO function block

Signals

Table 228:
TEIGGIO Input signals
Name
Type
BLOCK
BOOLEAN
IN
BOOLEAN
RESET
BOOLEAN
Table 229:
TEIGGIO Output signals
Name
Type
WARNING
BOOLEAN
ALARM
BOOLEAN
OVERFLOW
BOOLEAN
ACCTIME
REAL
Default
Description
0
Freeze the integration and block the other outputs
0
The input signal that is used to measure the
elapsed time, when its value is high
0
Reset the integration time
Description
Indicator of the integrated time has reached the
warning limit
Indicator of the integrated time has reached the
alarm limit
Indicator of the integrated time has reached the
overflow limit
Integrated elapsed time in seconds
1MRK 505 288-UEN A
Technical manual