Section 11
11.1
11.1.1
11.1.2
11.1.3
Technical manual
Logic

Tripping logic common 3-phase output SMPPTRC

Identification

Function description
Tripping logic common 3-phase output

Functionality

A function block for protection tripping is provided for each circuit breaker involved
in the tripping of the fault. It provides a settable pulse prolongation to ensure a three-
phase trip pulse of sufficient length, as well as all functionality necessary for correct
co-operation with autoreclosing functions.
The trip function block also includes a settable latch functionality for breaker lock-
out.

Function block

SMPPTRC
BLOCK
TRIP
TRIN
CLLKOUT
SETLKOUT
RSTLKOUT
IEC09000284_1_en.vsd
IEC09000284 V1 EN
Figure 119:
SMPPTRC function block
IEC 61850
IEC 60617
identification
identification
SMPPTRC
I->O
SYMBOL-K V1 EN
Section 11
Logic
ANSI/IEEE C37.2
device number
94
273