Section 11
Logic
11.1.4
11.1.5
Table 181:
SMPPTRC Group settings (basic)
Name
Operation
tTripMin
Table 182:
SMPPTRC Group settings (advanced)
Name
TripLockout
AutoLock
11.1.6
274

Signals

Table 179:
SMPPTRC Input signals
Name
BLOCK
TRIN
SETLKOUT
RSTLKOUT
Table 180:
SMPPTRC Output signals
Name
TRIP
CLLKOUT

Settings

Values (Range)
Unit
Off
-
On
0.000 - 60.000
s
Values (Range)
Unit
Off
-
On
Off
-
On

Operation principle

The duration of a trip output signal from tripping logic common 3-phase output
SMPPTRC is settable (tTripMin). The pulse length should be long enough to secure
the breaker opening.
For three-phase tripping logic common 3-phase output, SMPPTRC has a single input
(TRIN) through which all trip output signals from the protection functions within the
IED, or from external protection functions via one or more of the IEDs binary inputs,
are routed. It has a single trip output (TRIP) for connection to one or more of the IEDs
binary outputs, as well as to other functions within the IED requiring this signal.
Type
Default
Description
BOOLEAN
0
Block of function
BOOLEAN
0
Trip all phases
BOOLEAN
0
Input for setting the circuit breaker lockout function
BOOLEAN
0
Input for resetting the circuit breaker lockout
function
Type
Description
BOOLEAN
General trip signal
BOOLEAN
Circuit breaker lockout output (set until reset)
Step
Default
-
On
0.001
0.150
Step
Default
-
Off
-
Off
1MRK 505 288-UEN A
Description
Operation Off / On
Minimum duration of trip output signal
Description
On: Activate output (CLLKOUT) and trip
latch, Off: Only output
On: Lockout from input (SETLKOUT) and
trip, Off: Only input
Technical manual