Disturbance Report Drprdre; Identification; Function Block; Signals - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 12
Monitoring
12.4.2
12.4.2.1
12.4.2.2
12.4.2.3
12.4.2.4
Table 274:
DRPRDRE Non group settings (basic)
Name
Operation
PreFaultRecT
PostFaultRecT
TimeLimit
PostRetrig
Table continues on next page
348
used to get information about the recordings. The disturbance report files may be
uploaded to PCM600 for further analysis using the disturbance handling tool.

Disturbance report DRPRDRE

Identification

Function description
Disturbance report

Function block

DRPRDRE
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000346-1-en.vsd
IEC09000346 V1 EN
Figure 156:
DRPRDRE function block

Signals

Table 273:
DRPRDRE Output signals
Name
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED

Settings

Values (Range)
Unit
Off
-
On
0.05 - 9.90
s
0.1 - 10.0
s
0.5 - 10.0
s
Off
-
On
IEC 61850
identification
DRPRDRE
DRPOFF
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Step
Default
-
Off
0.01
0.10
0.1
0.5
0.1
1.0
-
Off
1MRK 505 288-UEN A
IEC 60617
identification
-
Description
Disturbance report function turned off
Disturbance recording started
Disturbance recording made
All disturbances in the disturbance report cleared
More than 80% of memory used
Description
Operation Off/On
Pre-fault recording time
Post-fault recording time
Fault recording time limit
Post-fault retrig enabled (On) or not (Off)
ANSI/IEEE C37.2
device number
-
Technical manual