Measured Values; Monitored Data; Operation Principle - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
12.14.6
12.14.7
12.14.8
Technical manual

Measured values

Table 304:
SPVNZBAT Measured values
Name
Type
U_BATT
REAL
BLOCK
BOOLEAN

Monitored Data

Table 305:
SPVNZBAT Monitored data
Name
Type
BATTVOLT
REAL

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The function execution requires that at least one of the function
outputs is connected in configuration.
The operation of the station battery supervision function can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.
GUID-9ACD1EE5-61C1-4CB8-9AF0-6F43292FC547 V2 EN
Figure 167:
Functional module diagram
The battery rated voltage is set with the RtdBattVolt setting. The value of the
BattVoltLowLim and BattVoltHiLim settings are given in relative per unit to the
RtdBattVolt setting.
It is possible to block the function outputs by the BLOCK input.
Default
Description
0.00
Battery terminal voltage that has to be supervised
0
Blocks all the output signals of the function
Values (Range)
Unit
-
kV
Section 12
Monitoring
Description
Service value of the
battery terminal voltage
393

Advertisement

Table of Contents
loading

Table of Contents