Function Block; Signals - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 10
Control
10.1.3
10.1.4
162

Function block

SESRSYN
U3PBB1*
SYNOK
U3PBB2*
AUTOSYOK
U3PLN1*
AUTOENOK
U3PLN2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
B1QOPEN
TSTENOK
B1QCLD
USELFAIL
B2QOPEN
B1SEL
B2QCLD
B2SEL
LN1QOPEN
LN1SEL
LN1QCLD
LN2SEL
LN2QOPEN
SYNPROGR
LN2QCLD
SYNFAIL
UB1OK
FRDIFSYN
UB1FF
FRDERIVA
UB2OK
UOKSC
UB2FF
UDIFFSC
ULN1OK
FRDIFFA
ULN1FF
PHDIFFA
ULN2OK
FRDIFFM
ULN2FF
PHDIFFM
STARTSYN
INADVCLS
TSTSYNCH
UDIFFME
TSTSC
FRDIFFME
TSTENERG
PHDIFFME
AENMODE
UBUS
MENMODE
ULINE
MODEAEN
MODEMEN
IEC08000219_3_en.vsd
IEC08000219 V3 EN
Figure 69:
SESRSYN function block

Signals

Table 95:
SESRSYN Input signals
Name
Type
U3PBB1
GROUP
SIGNAL
U3PBB2
GROUP
SIGNAL
U3PLN1
GROUP
SIGNAL
U3PLN2
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKSYNCH
BOOLEAN
BLKSC
BOOLEAN
BLKENERG
BOOLEAN
B1QOPEN
BOOLEAN
Table continues on next page
Default
Description
-
Group signal for phase to earth voltage input L1,
busbar 1
-
Group signal for phase to earth voltage input L1,
busbar 2
-
Group signal for phase to earth voltage input L1,
line 1
-
Group signal for phase to earth voltage input L1,
line 2
0
General block
0
Block synchronizing
0
Block synchro check
0
Block energizing check
0
Open status for CB or disconnector connected to
bus1
1MRK 505 288-UEN A
Technical manual

Advertisement

Table of Contents
loading

Table of Contents