Busbar protection
Table of Contents

Advertisement

Section 7
Current protection
110
the temperature of the object is above the set lockout release temperature setting
ResLo.
The time to lockout release is calculated, That is, a calculation of the cooling time to
a set value.
æ
t
= - × ç
t
ln
ç
lockout release
_
è
EQUATION1177 V1 EN
In the above equation, the final temperature is calculated according to equation 15.
Since the transformer normally is disconnected, the current I is zero and thereby the
Θ
is also zero. The calculated component temperature can be monitored as it is
final
exported from the function as a real figure, TRESLO.
When the current is so high that it has given a start signal START, the estimated time
to trip is continuously calculated and given as analogue output TTRIP. If this
calculated time get less than the setting time Warning, set in minutes, the output
WARNING is activated.
ö
Q
- Q
final
lockout release
_
÷
÷
Q
- Q
ø
final
n
1MRK 505 288-UEN A
(Equation 21)
Technical manual