Settings; Operation Principle - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 11
Logic
11.8.5
11.8.6
304
Table 226:
IB16FCVB Output signals
Name
Type
OUT1
BOOLEAN
OUT2
BOOLEAN
OUT3
BOOLEAN
OUT4
BOOLEAN
OUT5
BOOLEAN
OUT6
BOOLEAN
OUT7
BOOLEAN
OUT8
BOOLEAN
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN

Settings

The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)

Operation principle

An example is used to explain the principle of operation: With integer 15 sent to and
received by the IB16FCVB function on the IEC 61850 the OUTx changes from 0 to
1 on each of the OUT1; OUT2 OUT3 and OUT4. All other OUTx (5≤x≤16) remains
0. The boolean interpretation of this is represented by the assigned values of each of
the outputs OUT1 = 1; and OUT2 = 2; and OUT3= 4; and OUT4 = 8. The sum of these
OUTx (1≤x≤4) is equal to the integer 15 received via the IEC 61850 network. The
remaining OUTx = 0 for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in
accordance with the Table 227. When not activated the OUTx has the value 0.
The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae: OUTx
x-1
= 2
The sum of the values of all activated OUTx = 2
to the integer value received over IEC 61850 to the IB16FCVB_1 function block.
The Integer to Boolean 16 conversion with logic node representation function
(IB16FCVB) will transfer an integer with a value between 0 to 65535 communicated
via IEC 61850 and connected to the IB16FCVB function block to a combination of
1MRK 505 288-UEN A
Description
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
x-1
where 1≤x≤16 will be equal
Technical manual