Functionality; Function Block; Signals; Settings - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 12
Monitoring
12.13.2
12.13.3
12.13.4
12.13.5
390

Functionality

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-high
limit. The measure value expander block MVEXP has been introduced to enable
translating the integer output signal from the measuring functions to 5 binary signals:
below low-low limit, below low limit, normal, above high limit or above high-high
limit. The output signals can be used as conditions in the configurable logic or for
alarming purpose.

Function block

MVEXP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC09000215-1-en.vsd
IEC09000215 V1 EN
Figure 165:
MVEXP function block

Signals

Table 298:
MVEXP Input signals
Name
Type
RANGE
INTEGER
Table 299:
MVEXP Output signals
Name
Type
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN

Settings

The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
Default
Description
0
Measured value range
Description
Measured value is above high-high limit
Measured value is between high and high-high limit
Measured value is between high and low limit
Measured value is between low and low-low limit
Measured value is below low-low limit
1MRK 505 288-UEN A
Technical manual

Advertisement

Table of Contents
loading

Table of Contents