Current protection
Four step phase overcurrent protection 3-phase
output OC4PTOC
Identification
Function description
Four step phase overcurrent protection
3-phase output
Functionality
The four step phase overcurrent protection function, 3-phase output OC4PTOC has an
inverse or definite time delay independent for step 1 and 4 separately. Step 2 and 3 are
always definite time delayed.
All IEC and ANSI inverse time characteristics are available.
The directional function is voltage polarized with memory. The function can be set to
be directional or non-directional independently for each of the steps.