Section 7 Current Protection; Four Step Phase Overcurrent Protection 3-Phase Output Oc4Ptoc; Identification; Functionality - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
Section 7
7.1
7.1.1
7.1.2
Technical manual
Current protection
Four step phase overcurrent protection 3-phase
output OC4PTOC

Identification

Function description
Four step phase overcurrent protection
3-phase output

Functionality

The four step phase overcurrent protection function, 3-phase output OC4PTOC has an
inverse or definite time delay independent for step 1 and 4 separately. Step 2 and 3 are
always definite time delayed.
All IEC and ANSI inverse time characteristics are available.
The directional function is voltage polarized with memory. The function can be set to
be directional or non-directional independently for each of the steps.
Second harmonic blocking level can be set for the function and can be used to block
each step individually
Current protection
IEC 61850
IEC 60617
identification
identification
OC4PTOC
3I>
4
alt
4
TOC-REVA V1 EN
Section 7
ANSI/IEEE C37.2
device number
51/67
79