Bay Control Qcbay; Identification; Functionality; Function Block - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
10.2.5
10.2.5.1
10.2.5.2
10.2.5.3
10.2.5.4
Technical manual

Bay control QCBAY

Identification

Function description
Bay control

Functionality

The Bay control QCBAY function is used together with Local remote and local
remote control functions to handle the selection of the operator place per bay. QCBAY
also provides blocking functions that can be distributed to different apparatuses within
the bay.

Function block

QCBAY
LR_OFF
PSTO
LR_LOC
UPD_BLKD
LR_REM
CMD_BLKD
LR_VALID
LOC
BL_UPD
REM
BL_CMD
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 76:
QCBAY function block

Signals

Table 110:
QCBAY Input signals
Name
Type
LR_OFF
BOOLEAN
LR_LOC
BOOLEAN
LR_REM
BOOLEAN
LR_VALID
BOOLEAN
BL_UPD
BOOLEAN
BL_CMD
BOOLEAN
Table 111:
QCBAY Output signals
Name
Type
PSTO
INTEGER
UPD_BLKD
BOOLEAN
CMD_BLKD
BOOLEAN
LOC
BOOLEAN
REM
BOOLEAN
IEC 61850
IEC 60617
identification
identification
QCBAY
-
Default
Description
0
External Local/Remote switch is in Off position
0
External Local/Remote switch is in Local position
0
External Local/Remote switch is in Remote
position
0
Data representing the L/R switch position is valid
0
Steady signal to block the position updates
0
Steady signal to block the command
Description
Value for the operator place allocation
Update of position is blocked
Function is blocked for commands
Local operation allowed
Remote operation allowed
Section 10
Control
ANSI/IEEE C37.2
device number
-
183

Advertisement

Table of Contents
loading

Table of Contents