1MRK 505 383-UEN A
11.5.3
11.6
11.6.1
Breaker protection REQ650 2.2 IEC
Application manual
Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via
the local HMI (Main Menu/Settings / IED Settings / Monitoring / Event
Function) or via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
The inputs can be set individually as:
•
NoEvents
•
OnSet, at pick-up of the signal
•
OnReset, at drop-out of the signal
•
OnChange, at both pick-up and drop-out of the signal
•
AutoDetect, the EVENT function makes the reporting decision (reporting
criteria for integers have no semantic, prefer to be set by the user)
LONChannelMask or SPAChannelMask
Definition of which part of the event function block that shall generate events:
•
Off
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
MinRepIntVal (1 - 16)
A time interval between cyclic events can be set individually for each input
channel. This can be set between 0 s to 3600 s in steps of 1 s. It should normally be
set to 0, that is, no cyclic communication.
It is important to set the time interval for cyclic events in an
optimized way to minimize the load on the station bus.
Disturbance report DRPRDRE
Identification
Function description
Disturbance report
Disturbance report
Disturbance report
IEC 61850 identification
DRPRDRE
A1RADR - A4RADR
B1RBDR - B22RBDR