16
TROUBLESHOOTING
To ad n troubleshootng, Parameters 50 through 60 can be accessed wthout enterng the
PASSWORD . Smply press the Mode button twce to "skp" over the PASSWORD prompt,
and "P50" wll be dsplayed to ndcate that the parameter menu has been entered and
Parameter 50 (FAULT HISTORY) can be vewed . The and buttons can then be used
to scroll from Parameter 50 to Parameter 60 . Once the desred parameter s found, press
the Mode button to vew ts "contents" . When finshed, press Mode to ext the parameter
menu . An example s shown heren:
Press Mode once
Dsplay reads "00"
Upper rght decmal pont blnks
Press Mode agan
Dsplay reads "P50" (FAULT HISTORY)
Use and to scroll to the desred
parameter number
(In ths example Parameter 54 has been
selected, whch s MOTOR LOAD)
Press Mode to vew parameter con-
tents (77 = 77% LOAD)
Upper rght decmal pont blnks
Press Mode agan to ext
In the example above, Parameter 54 - MOTOR LOAD s beng vewed . The "77" n the
example ndcates that the load on the motor s 77% of the output current ratng of the
drve .
The table heren lsts the fault condtons that wll cause the drve to shut down, as well
as some possble causes . Contact the factory for more nformaton on troubleshootng
faults .