14

PARAMETER MENU

NO.
PARAMETER NAME
01
LINE VOLTAGE
02
CARRIER FREQUENCY
03
START METHOD
04
STOP METHOD
STANDARD SPEED
05
SOURCE
06
RELAY OUTPUT
TB-13A FUNCTION
10
SELECT
TB-13B FUNCTION
11
SELECT
SM01M
RANGE OF ADJUSTMENT
HIGH (01), LOW (02)
4kHz (01), 6 kHz (02), 8 kHz (03), 10 kHz (04)
NORMAL (01), START ON POWER UP (02),
START WITH DC BRAKE (03),
AUTO RESTART WITH DC BRAKE (04),
FLYING RESTART 1 (05),
FLYING RESTART 2 (06),
FLYING RESTART 3 (07)
COAST (01), COAST WITH DC BRAKE (02),
RAMP (03), RAMP WITH DC BRAKE (04)
KEYPAD (01), PRESET #1 (02),
0-10 VDC (03), 4-20 mA (04)
NONE (01), RUN (02), FAULT (03),
INVERSE FAULT (04), FAULT LOCKOUT (05),
AT SET SPEED (06), ABOVE PRESET #3 (07),
CURRENT LIMIT (08), AUTO SPEED (09),
REVERSE (10)
NONE (01), 0-10 VDC (02), 4-20 mA (03),
PRESET SPEED #1 (04),
START FORWARD (05),RUN REVERSE (06),
START REVERSE (07),
EXTERNAL FAULT (08),
INVERSE EXT FAULT (09),
AUXILIARY STOP (10),
ACCEL/DECEL #2 (11)
NONE (01), 0-10 VDC (02), 4-20 mA (03),
PRESET SPEED #2 (04), DECREASE FREQ (05),
START FORWARD (06), JOG FORWARD (07),
JOG REVERSE (08), EXTERNAL FAULT (09),
INVERSE EXT FAULT (10), AUX. STOP (11),
ACCEL/DECEL #2 (12), REMOTE KEYPAD (13)
28
FACTORY
DEFAULT
HIGH (01)
6 kHz (02)
NORMAL (01)
COAST (01)
KEYPAD (01)
NONE (01)
NONE (01)
NONE (01)