04 RAMP WITH DC BRAKE: When a stop command s gven, the drve wll decelerate
the motor down to 0 .2 Hz (at the rate set by Parameter 20 - DECELERATION TIME)
and then actvate DC brakng accordng to the settngs of Parameters 21 - DC BRAKE
TIME and 22 - DC BRAKE VOLTAGE . Ths s used to brng the load to a final stop,
as the motor may stll be turnng slghtly after the drve stops .
P05
STANDARD SPEED SOURCE
P05 selects the speed reference source when the drve s n STANDARD speed mode .
The followng speed references can be selected:
01 KEYPAD: Use the  and  buttons to scroll to the desred speed .
02 PRESET SPEED #1: Drve wll operate at the frequency set n Parameter 31 .
03 0-10 VDC: Drve wll respond to a 0-10 VDC sgnal wred to TB-5 (+) and TB-2 (-) .
04 4-20 mA: Drve wll respond to a 4-20 mA sgnal wred to TB-25 (+) and TB-2 (-) .
P06
RELAY OUTPUT
P06 selects the status ndcaton for the normally open relay output at TB-16 and TB-17:
01 NONE: Dsables the relay output .
02 RUN: Closes upon a START command . Opens f the drve s n a STOP state, the
drve faults, or nput power s removed . DC brakng s consdered a STOP state .
03 FAULT: Closes f there s no fault condton . Opens f the drve faults, or nput power
s removed .
04 INVERSE FAULT: Closes f the drve faults . Opens f there s no fault condton .
05 FAULT LOCKOUT: Closes when nput power s appled . Opens f three restart attempts
are unsuccessful, or f nput power s removed .
06 AT SET SPEED: Closes f the drve s wthn + 0 .5 Hz of the speed setpont .
07 ABOVE PRESET SPEED #3: Closes f the output frequency exceeds PRESET
SPEED #3 (Parameter 33) . Opens f the output frequency s equal to or less than
PRESET SPEED #3 .
08 CURRENT LIMIT: Closes f the output current exceeds the CURRENT LIMIT settng .
Opens f the output current s equal to or less than CURRENT LIMIT (see Parameter
25) .
09 AUTOMATIC SPEED MODE: Closes f an AUTOMATIC (termnal strp) speed
reference s actve . Opens f a STANDARD (Parameter 5) speed reference s
actve .
10 REVERSE: Closes when reverse rotaton s actve . Opens when forward rotaton s
actve (see Parameter 17 - ROTATION DIRECTION) .
33
SM01M