11.3
Three-Wire Start/Stop Control
1
2
5
-
+
Momentary
STOP
Contact
NOTE
•
Program TB-13E (Parameter 12) for START FORWARD (06) .
•
If reverse drecton s requred, set ROTATION (Parameter 17) to FORWARD
AND REVERSE (02), and program TB-13A (Parameter 10) for START
REVERSE (07) .
•
Momentarly close TB-13E to TB-11 to START n the forward drecton, or close
TB-13A to TB-11 to START n the reverse drecton . Momentarly open TB-1 to
TB-11 to STOP the drve .
•
For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE
(Parameter 05) to 0-10 VDC (03) or 4-20 mA (04) .
SM01M
11
6
13A
REV
Momentary
START
Contact
3-Wre Start/Stop Control
13B
13E
25
+
FWD
20
FORM A RELAY
17
16