Input Wire Size Requirements
120 Vac 1 phase
MODEL
AWG mm
SM004S
14
SM005S
14
SM010S
12
SM015S
10
7.4
Installation According to EMC Requirements
The SCM and SCL Seres can be nstalled to meet the European standards for
Electromagnetc Compatblty (EMC) requrements . These requrements govern the
permssble electromagnetc emssons and mmunty, both radated and conducted, of
a drve system .
The EMC requrements apply to the final nstallaton n ts entrety, not to the ndvdual
components used . Because every nstallaton s dfferent, the recommended nstallaton
should follow these gudelnes as a mnmum . Addtonal equpment (such as ferrte core
absorbers on power conductors) or alternatve wrng practces may be requred to meet
conformance n some nstallatons .
Filter: The nput to the drve (or group of drves) must nclude a filter to reduce the electrcal
nose reflected back to the AC Lne . The SCL Seres ncludes a filter that has been tested
to meet the ndustral standards set by the EU, EN 61800-3 for conducted emssons and
EN 55011 for radated emssons to class A complance when nstalled n a control cabnet
wth a motor cable < 10m . The SCM can be nstalled to meet these same standards when
used wth an approprately nstalled external lne filter .
EMC
Complance wth EN 61800-3/A11
Installation: Shelded cable must be used for all control and power cables
and exposed wrng must be kept as short as possble .
Screen clamps
A
Control cable
B
Low-capactance motor cable
C
(core/core < 75 pF/m, core/screen < 150 pF/m)
Electrcally conductve mountng plate
D
Flter
E
SM01M
INPUT WIRE SIZE REQUIREMENTS
208/240 Vac 1 phase
MODEL
AWG mm
2
2.5
S_204S
14
2.5
S_205S
14
S_208S
14
4.0
S_210S
14
6.0
S_215S
14
S_220S
12
S_230S
10
208/240 Vac 3 phase
MODEL AWG mm
2
2.5
2.5
SM205
14
2.5
2.5
SM210
14
2.5
SM215
14
4.0
SM220
14
6.0
SM230
14
SM250
12
SM275
8
SM2100
8
SM2150
6
12
400/480 Vac 3 phase
MODEL AWG mm
2
2.5
SM405
14
2.5
SM410
14
2.5
SM415
14
2.5
SM420
14
2.5
SM430
14
4.0
SM450
14
10
SM475
12
10
SM4100
10
16
SM4150
8
B
C
A
2
2.5
2.5
2.5
2.5
2.5
2.5
4.0
6.0
10
E
D
SM01 1