TB-13A FUNCTION SELECT
P10 selects the functon of termnal TB-13A . Closng TB-13A to TB-11 (or openng n
the case of settngs 08 and 10) actvates the selected functon . The followng functons
can be selected:
01 NONE: Dsables the TB-13A functon .
02 0-10 VDC: Selects a 0-10 VDC sgnal (at TB-5) as the AUTO speed reference
nput .
03 4-20 mA: Selects a 4-20 mA sgnal (at TB-25) as the AUTO speed reference nput .
04 PRESET SPEED #1: Selects PRESET SPEED #1 as the speed reference . The drve
wll operate at the frequency programmed nto Parameter 31 .
05 START FORWARD: Sets up the drve for a 3-wre start/stop crcut . Momentarly close
TB-13A to TB-11 to start the drve, and momentarly open TB-1 to TB-11 to stop .
06 RUN REVERSE: Close TB-13A to TB-11 to run n the reverse drecton, and open
to stop . Close TB-1 to TB-11 to run n the forward drecton and open to stop .
07 START REVERSE: Momentarly close TB-13A to TB-11 to start the drve n the reverse
drecton, and momentarly open TB-1 to TB-11 to stop . Parameter 17 - ROTATION
must be set to FORWARD AND REVERSE (02), and TB-13E must be used for
START FORWARD .
08 EXTERNAL FAULT: Sets TB-13A as a normally closed external fault nput . Open
TB-13A to TB-11 to trp the drve .
09 INVERSE EXTERNAL FAULT: Sets TB-13A as a normally open external fault nput .
Close TB-13A to TB-11 to trp the drve .
10 AUXILIARY STOP: When TB-13A s opened wth respect to TB-11, the drve wll
decelerate to a STOP (even f STOP METHOD s set to COAST) at the rate set nto
ACCEL/DECEL #2 (Parameter 42) .
11 ACCEL/DECEL #2: Selects the acceleraton and deceleraton tme programmed nto
ACCEL/DECEL #2 (Parameter 42) .
P11
TB-13B FUNCTION SELECT
P11 selects the functon of termnal TB-13B . Closng TB-13B to TB-11 (or openng n
the case of settngs 09 and 11) actvates the selected functon . The followng functons
can be selected:
01 NONE: Dsables the TB-13B functon .
02 0-10 VDC: Selects a 0-10 VDC sgnal (at TB-5) as the AUTO speed reference
nput .
03 4-20 mA: Selects a 4-20 mA sgnal (at TB-25) as the AUTO speed reference nput .
04 PRESET SPEED #2: Selects PRESET SPEED #2 as the speed reference . The drve
wll operate at the frequency programmed nto Parameter 32 .