Startup Current Rise Settings; Step Current Change Settings; Figure 43: Advanced Ccr Ramp Settings - Eaton Crouse-Hinds Series Instruction Manual

Switchgear constant current regulator
Hide thumbs Also See for Crouse-Hinds Series:
Table of Contents

Advertisement

PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829
IMPORTANT
11.6

Startup Current Rise Settings

The startup current rise setting determines how fast the CCR will reach the required current starting
from a de-energized state.
Available values: (default value is 4)
1 – 0. 5 Amp per second
2 – 1 Amp per second
3 – 4 Amps per second
4 – 6 Amps per second
11.7

Step Current change Settings

The step current rise setting determines how fast the CCR will adjust the output current when moving
between steps.
Available values: (default value is 4)
1 – 1. 5 Amp per second
2 – 3 Amp per second
3 – 4 Amps per second
4 – 5 Amps per second
Instruction Manual
Series 82_SGSPR-480- _ _ - _ - _
These setting should only be adjusted by an Eaton Crouse-Hinds
certified engineer for specific field condition. Please contact Crouse-
Hinds support for additional information.

Figure 43: Advanced CCR Ramp Settings

WARNING:
67
DOCUMENT 1222
REV. A