Figure 29: Outputs group
86
AC 1006.9 - 5/03
Chapter 7 - Settings and configuration

7:2.4.6 Outputs

Start / Stop
Protections
Warnings
Faults
Inputs
Outputs
Fieldbus
Seq. Start
To set parameters related to the programmable outputs,
enter the Outputs group.
Relay K4
Select the required function for output relay K4.
One of the following functions can be selected:
Run
Run indication.
TOR
Top of ramp indication.
Event
Indication of selected event(s) . The following
events can be selected individually:
Motor overload protection
Fault
High current protection
SCR overload protection
Locked rotor protection
Underload protection
Phase imbalance protection
PTC protection
Phase reversal protection
Overload warning
SCR overload warning
High current warning
Low current warning
Press Store to save/activate the selected function.
Relay K5
Select the required function for output relay K5.
One of the following functions can be selected:
Run
Run indication.
TOR
Top of ramp indication.
Event
Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.